Can a Washington crawl space have no vents at all?
R408.3 lists two numbered items for a Washington crawl space without vents: (1) a sealed Class I liner run up the stem wall, with an Appendix AF radon system; (2) a continuously running exhaust fan at 1 cfm per 50 square feet of floor. The text doesn't say whether both must be met, so the building official confirms how the items apply to your design.
Does a dehumidifier meet Washington's unvented crawl space rule?
No dehumidifier option appears in Washington's R408.3; the amended text names continuous mechanical exhaust to the outside. A dehumidifier may be installed as well, but it is only ever an addition to the exhaust fan, never a replacement for it.
Are unvented crawl spaces allowed in Spokane County?
Washington's Appendix AF lists Spokane among seven high radon potential counties, with Clark, Ferry, Okanogan, Pend Oreille, Skamania and Stevens, and says unvented crawl spaces are not permitted in any of them. Confirm with the county or city building department how that applies to an existing house.
What size exhaust fan does an unvented crawl space need?
Divide the crawl space floor area by 50 to get the minimum exhaust in cubic feet per minute: 1,000 square feet needs 20 cfm and 1,800 square feet needs 36 cfm. The fan runs continuously and must vent to the outside, not into the house or the attic.
Is the black poly ground cover rule the same as the Class I vapor retarder rule?
The two rules are different. R408.1 sets six-mil black polyethylene or an approved equal for every crawl space. The reduced-vent and unvented designs call for a Class I vapor retarder, a tighter class of material, and the unvented design adds sealed seams and a stem-wall seal.
Who decides whether my crawl space project meets the code?
Your city or county building official decides, because local building departments enforce the state code and interpret it for each project. Email before work starts, describe the design, and keep a note of the answer and any permit and inspection records.
Does reducing the vents trigger the radon rules?
Reducing vent area below 1 square foot per 300 square feet, or installing operable louvers, triggers a radon vent under the R408.2 exception. The pipe starts between the ground cover and the soil and is built to Appendix AF.